GWS and GMRS selection
Heat shrink sleeve size chart for wraparound repairs
Size on the two diameters the part has to clear and then grip, not on the damage you can see.
Water gets into a repair that recovered onto air. The wall closed over a lug or a bulge of armour, never reached the jacket beside it, and left a channel no adhesive could bridge. Nobody sees it. It shows up as a fault two winters later, at the same trench, on a cable that was supposedly fixed.
That is a sizing failure and not an installation failure. It happens whenever the diameter you measured is not the diameter the part has to work against.
The rule is one line. Supplied diameter above the largest outside diameter it must pass over. Recovered diameter below the smallest outside diameter it must grip. A row that satisfies one half and fails the other is the wrong row, whatever its cable range column says.
So measure the extremes. Take the outside diameter over the largest obstruction inside the repair length: a connector body, an armour clamp, tape build-up left by whoever went in before you. Then take the bare jacket diameter where the sleeve has to seal down, clear of the damage at both ends. Those two numbers decide the code. The width of the split decides nothing.
Two families sit below and they answer two different repairs. GWS is the wraparound sleeve, folded around the cable or pipe and zipped shut with a stainless steel channel. GMRS is the cable repair sleeve, folded around and taped up with heat-resistant tape before shrinking. Neither needs the cable cut and neither needs the system shut down.
This chart exists in two published versions and they do not agree
The manufacturer's web page for the wraparound sleeve and the manufacturer's printed datasheet give different cable ranges for the same GWS codes. GWS-140/35 is 105-45 mm on the web page and 122-38 mm on the sheet. The same split runs through GWS-55/8, GWS-105/28, GWS-190/46 and GWS-240/50. The recovered wall tolerance differs too: the web page prints plus or minus 10 percent, the datasheet prints plus or minus 20 percent. One code appears only on the web page and one only on the sheet. Both columns are reproduced below, unaltered. Where they differ, size against the narrower datasheet band and get the code confirmed in writing before the order goes out.
GWS wraparound sleeve, supplied and recovered
| Gala code | Supplied dia. | Recovered dia. | Recovered wall | Cable range, datasheet | Cable range, web page |
|---|---|---|---|---|---|
| GWS-34/10 | 34 | 10 | 2.7 | 30-10 | not listed |
| GWS-55/8 | 55 | 8 | 2.7 | 42-8 | 42-10 |
| GWS-76/18 | 76 | 18 | 2.7 | 62-22 | 62-22 |
| GWS-105/28 | 105 | 28 | 2.7 | 92-30 | 85-35 |
| GWS-140/35 | 140 | 35 | 2.7 | 122-38 | 105-45 |
| GWS-160/55 | 160 | 55 | 2.7 | not listed | 130-58 |
| GWS-190/46 | 190 | 46 | 2.7 | 160-50 | 150-60 |
| GWS-240/50 | 240 | 50 | 2.7 | 200-55 | 200-70 |
All dimensions in millimetres. Recovered wall is 2.7 mm on every code; the datasheet gives that wall as plus or minus 20 percent and the web page as plus or minus 10 percent. Maximum available length is 1500 mm. A cell reading not listed means one source publishes that code and the other omits it. Datasheet columns are from the manufacturer's wraparound sleeve sheet, Issue 2, October 2024 and from the combined Cable Repair Sleeves sheet, which is the only source carrying GWS-34/10.
GMRS cable repair sleeve, cable OD and overlap
| Gala code | Cable OD | Length options | Minimum overlap |
|---|---|---|---|
| GMRS-19 | 5 - 10 | 100 / 200 / 300 | 25 |
| GMRS-30 | 8 - 17 | 100 / 200 / 300 | 25 |
| GMRS-40 | 12 - 28 | 100 / 200 / 300 | 25 |
| GMRS-70 | 24 - 55 | 100 / 200 / 300 | 25 |
| GMRS-115 | 40 - 85 | 100 / 200 / 300 | 50 |
| GMRS-160 | 55 - 122 | 300 / 400 | 50 |
| GMRS-180 | 60 - 132 | 300 / 400 | 75 |
| GMRS-200 | 65 - 150 | 300 / 400 | 75 |
| GMRS-250 | 75 - 192 | 300 / 400 | 75 |
| GMRS-565 | 60 - 132 | 300 / 400 | 75 |
| GMRS-628 | 65 - 150 | 300 / 400 | 75 |
| GMRS-785 | 75 - 192 | 300 / 400 | 75 |
All dimensions in millimetres. Overlap is a published minimum and not a target. The last three codes appear on the datasheet only, and each repeats the cable band and length options of the code three rows above it; the sheet does not say what separates them, so confirm which one you are being offered before specifying it.
Longitudinal change is not published for either series
How much a sleeve pulls back along its own axis decides whether the ends stay on the sealing land. The manufacturer prints a limit of minus 10 percent maximum on its heat shrink tubing datasheets, the method most often cited being ASTM D2671. Neither the wraparound chart nor the repair sleeve chart repeats that figure, so it cannot be read across to GWS or GMRS here. Order length for the shrink rather than for the gap, and ask the manufacturer to confirm the limit in writing for the code you have chosen.
Reading a row without getting it wrong
This sequence is our reading of the two published charts. It is not a manufacturer's instruction, and anything supplied with the part overrides it.
Measure over the largest obstruction
Take the outside diameter over whatever is biggest inside the repair length, not over the clean jacket beside it. That figure must come in under the supplied diameter, or the part will not close around the cable at all.
Measure the smallest land it must seal onto
Take the jacket diameter where the sleeve ends will sit, beyond the damage. That figure must sit above the recovered diameter, or the wall stops before it touches and you have built the void described at the top of this page.
Test both halves of the same row
GWS-105/28 passes over anything under 105 mm and grips anything over 28 mm. Two adjacent rows will often accept your obstruction and only one of them will still grip your land.
Check the lap survives at your diameter
The sheet has to wrap past itself by the row's published minimum, measured around the circumference. On GMRS-115 that is 50 mm of lap and on GMRS-250 it is 75 mm. A part trimmed to suit a smaller cable loses its lap well before it loses its fit.
Choose the supplied length last
GMRS is fixed at 100, 200, 300 or 400 mm depending on the code, and the wraparound runs to 1500 mm. Cover the damage plus a land at both ends, then satisfy yourself the shrink will not drag those ends off it.
The six words the two charts use
- Supplied diameter
- The internal diameter the part arrives at, before any heat. On GWS it is the first number in the code. GWS-160/55 arrives at 160 mm.
- Recovered diameter
- The internal diameter the part reaches with nothing inside it, unrestrained. GWS-160/55 recovers to 55 mm. Over a cable you never see that figure, because the substrate arrests the shrink first.
- Recovered wall
- The wall thickness at full recovery, 2.7 mm across the whole GWS range. It is a fully recovered figure. The chart publishes no wall for a part held open on a cable, which is every part in service.
- Shrink ratio
- Supplied internal diameter divided by fully recovered internal diameter, achieved unrestrained and with nothing in the way. The repair sleeve is published at 3:1. The wraparound chart publishes no ratio at all, and its own two columns imply a much larger reduction: GWS-55/8 goes from 55 mm to 8 mm. Treat a ratio as a ceiling rather than a promise. The same manufacturer's tubing reference works the arithmetic through at shrink-tube.com.
- Overlap length
- How far the sheet laps past itself around the circumference once it is closed. It steps 25, 50 and 75 mm as the codes get larger, and every published figure is a minimum. What happens at that seam when the lap is short is set out on why these repairs fail.
- Cable range
- The band of cable outside diameters a row is published against. This is the column that moves between the two versions of the GWS chart, so quote the code and the source together rather than the band on its own.
Where the other dimensions live
This page carries cable dimensions and nothing else. Two other substrates have charts of their own, and no figure above transfers to either.
- Pipeline weld joints, 159 to 1016 mmThe GTWS three-layer sleeve is sized on pipeline outside diameter and supplied with a separate closure patch. Nothing on this page applies to it.
- Pre-insulated pipe endsSealing caps are sized on the casing and the service pipe together, single or double outlet, never on a cable band.
- Closing the sleeve without trapping a voidThe channel, the heating pattern, and the temperature-sensitive paint that tells you the shrink has finished.
- Wraparound or tubularIf you can reach a free end, a different part and a different chart apply.
- Repairing distribution cable and conductor in serviceWhat a jacket repair does and does not do to a conductor that is still live.
Send the two diameters, not the cable size
A quote comes back correct first time when it carries the outside diameter over the largest obstruction, the jacket diameter at the sealing land, the damage length and the quantity. Give the GWS or GMRS code you read off, and say which of the two published charts you read it from.